"建筑"
"第 页"
"2009年市区建筑工程安全生产与文明施工(一季度)项目检查汇总表 "
"序号","项 目 名 称","项目地点","监理单位","总监","施工单位","项目 经理","安全员","检查 得分","备注(存在主要问题)"
1,"华润置地平门府","原阀门厂","园区建设监理","雷建平","苏州建鑫","陈金根","陈 宏蒋丁元",85.7,"脚手板局部破损,檐口处悬挑段脚手缺斜撑,有的立面缺安全网,井字架卸料平台缺防护,侧面防护不严,有的设备进线无PE线,地下室顶板上缺防护栏杆."
2,"苏州万达商业广场","312国道北,车管所西侧","江苏建科","储复环","中建二局","白书庭","郑 宏付志强匡彦博",71.9,"A2房电影厅模板支架搭设严重不符方案,未经支架体系验收即铺模板,砼搅拌机缺吊构保险,室内电缆随地拖拉,有的设备进线无PE线,箱内电器装置未固定牢靠,总箱电流表损坏,一闸多用,电缆老化.西南角处脚手架局部立杆偏大,内挡大无防护,室内洞口,电梯井内防护不严密,安全网局部破损,剪刀撑未到顶,现场缺防火措施,现场文明施工差,西南角围栏缺少,基坑上沿堆载过大,在建工程住人."
3,"苏州站改造","苏站路","上海天佑监理","陈守俊","中铁十二局","董宝贵","杨俊明",82.8,"基坑上沿缺挡水墙,钢支撑个别处处缺螺栓,有的端头板与墙体不密贴,托架与支撑缺木楔,支撑上余土未及时清理,纵坡坡比较小,未按分层分段的要求进行土方开挖,降压管与支撑未作连结,电缆浸泡在水中,土方运输通道坡角处积水未及时排除,工人普遍不扣帽带,门口无冲洗平台及沉淀池,带泥上路.下沉广场模板支架侧向缺斜撑,顶托下却纵横向水平杆,钢管未检测."
4,"火车站站前北广场地下空间(一期),汽车客运站工程",,"南京南房建设监理","陈彩朋","苏州一建","刘军","施汉涛邵文权","未打分","安全教育不全,对部分新进场人员未及时进行安全教育并考核,专项安全教育未形成会议记录,教育档案不全,与分包单位未签订安全协议,现场未建立安全生产领导小组.电缆老化,机械设备(桩机)未进场验收,工人安全帽佩戴不规范."
5,"火车站站前北广场地下空间(二期),公交换乘楼",,"园区监理","桑林华","苏州一建","罗惠生","张荣祥夏伟","未打分","日常安全检查不到位,基坑缺临边防护,施工用电电缆随地拖拉,未作埋地或架空,箱内电器装置不符,接线较乱,现场排水设施未贯通,缺三级沉淀池和冲洗平台.C区车道基坑上沿堆置土方离基坑过近,对上水管和煤气管监测点布置不符要求."
6,"苏州美术馆文化馆名人馆新馆桩基工程",,"中咨监理","佘文庆","苏州建院营造","宋志兵","谢余飞","未打分","钢筋弯曲机无防护棚,作业人员未经考核合格,桩机卷扬机缺绳筒保护,桩孔未及时回填或覆盖,泥浆泵缺开关箱,不符"三级配电,二级保护"的要求,项目经理不在场,缺少安全生产规章制度与安全生产责任制,电缆随地拖拉,设备进线无PE线,缺重复接地,有的箱子装置不全,一闸多用."
7,"技侦业务用房扩建工程",,"苏州中润","王三男","南通二建","陈建新","刘建力",,"未施工"
8,"苏站路农贸市场建设工程","苏锦路北","苏州市晨阳监理","张琪","常熟虞城建筑","戴国华","应忠华",74.5,"电梯井内无内隔离措施,防护门高度不够,井架无独立卸料平台,平台横杆变形严重,脚手架拉结偏少,无通道口防护棚,阴角缺立杆,门洞处缺斜杆.北侧配电房脚手架与外输电线无安全距离,无防护措施,井架附墙与脚手拉结,砼搅拌机缺吊钩保险."
9,"仲雅苑","清塘北路东侧,312国道北侧","建园监理","葛成刚","浙江中成","裘宝根","裘宝国",75,"脚手架上建筑垃圾较多,安全网破损,5号房前砼搅拌机皮带轮和齿轮无防护罩,5号房前卷扬机旁一电箱内装置不符,采用熔断器,无总,分路隔离开关,设备用线无插头,有的设备PE线未跟出,9号房井架卸料平台变形严重,侧面无剪刀撑,电焊机桩头外露,箱内有的出线未经漏电保护,砂浆机采用倒顺开关,井架卸料平台安全门未关闭,侧面及正面防护不严密."
10,"仲雅苑南区二期工程",,"苏州建园","肖大林","苏州天一建筑","徐美华","汤国栋余 明",79,"13号房脚手架副立杆与大横杆连接不符要求,14号房安全网未及时张挂,塔吊基础积水,节前复工前的安全检查和安全教育未见记录,宿舍内有烧煮现象,工地上有吸游烟(木工间),电缆随地拖拉未穿管保护,保护接地与保护接零混用.模板支撑缺纵横向扫地杆,主节点处缺水平杆."
11," 金阊新城小学",,"苏州恒信监理","沈鹤鸣","苏州一建","裴家鼎","王晔 陈军贤",83,"工人安全教育考核未批卷,个别设备未搭设防护棚,塔吊基础有少许积水,个别栋号无通道口防护棚,架子工未佩戴安全帽,个别电箱内接线乱,钢筋机械电缆随地铺设未穿管保护,个别立面脚手架底未硬化,体育馆基坑上沿脚手架立杆未对接,有的脚手架缺脚手板."
12,"金阊新城幼儿园",,"苏州恒信监理","沈鹤鸣","苏州一建","游必武","郁银刚徐文男",82.4,"脚手架上建筑垃圾未及时清理,建筑垃圾较多,一宿舍内有烧煮现象,电缆埋地不规范,切割机无末端开关箱,井架门未封闭,缺通道口防护棚."
13,"苏州车市二期","五金城312国道对面","建筑监理","施启昌","顺龙建设","宋小涵","朱从兵虞家之",73.3,"有的脚手架低于檐口,安全网张挂不严密,脚手板破损,建筑垃圾未及时清理,内挡大无防护,8#房楼层内电梯井无任何防护,个别电箱内采用螺旋熔断器,三级教育无考试试卷,圆盘机采用倒顺开关,现场接线使用家用联合插座,井架卸料平台无防护门,栋号间通道搭设不稳固,食堂不卫生."
14,"传化物流一期A区","白洋湾","华铁监理","徐瑞鑫","浙江圣华","张若庄","王正海徐叶定",77.3,"井架卸料平台无防护门,侧面无剪刀撑,机房屋面模板支架板底缺纵横向水平杆,部分立杆长细比较大,脚手架低于女儿墙,检查整改记录不闭合,专职安全员不到位,一闸多用,电线无插头,电缆随地铺设未穿管保护,井架基础积水.作业人员普遍不戴安全帽,楼层伸缩缝未封闭,室内部分洞口无防护,脚手架竹笆片未满铺,脚手架基础泡在水中."
15,"金阊区国资商务楼","西环路东侧","江苏众信","顾 峰","建设集团","钱伟","吴学海袁振华",85.3,"部份脚手架内档防护不到位,架体上建筑垃圾未及时清除,部份楼层临边,预留洞口防护不到位,部份特殊工种人员操作证过期,无复审记录."
16,"大观名园3标","清塘路","新民监理","梁广文","江苏中厦","王久康","应开明柏宝荣",,"现场项目部管理人员,工人都没到位,无法检查"
17,"御庭苑工程及车库","西园路","东大监理","于小平","苏州建鑫","范丽君","张政荣王玉良",,"扫尾阶段,未打分"
18,"住宅商业用房(金阊项目样板段)工程",,"天平监理","王宪龙","浙江大经建设","林高彬","冯志华",79,"临时施工用电不符合JGJ46-2005规范,部份机具缺未端电箱,部份电箱箱体破损未及时更换,修复,部份脚手架内档防护不到位,拉结点少,部份楼层临边,预留洞口防护不到位,部份特殊工种人员操作证过期,无复审记录,现场安全警示警告标志少,消防器材少,安全资料记录不全."
19,"玖园住宅小区","北环西路","卓越监理","宋红卫","浙江丰惠建设集团","陈镇龙","周杏林柯洪春",72,"少量工人在现场整理,尚未正常施工"
20,"原合成化工厂定销房2007-G-13地块小区工程(鼎尚花园)",,"吴江建设监理","张勇","江苏启安建设集团","朱兴东","蒋永生",84,"临时施工用电不符合JGJ46-2005规范,电线随意拖拉,部份脚手架内档防护不到位,拉结点少,部份楼层临边,预留洞口防护不到位,部份特殊工种人员操作证过期,无复审记录,现场安全警示警告标志少,消防器材少,安全资料记录不全."
21,"苏州新庄二村34#,35#住宅工程",,"苏州正建监理","仇美芳","中建三局","张云泰","杨丽",72,"少量工人在现场整理,尚未正常施工"
22,"中天西园路项目","西园路","时代监理","潘东平","浙江展诚建设集团","朱信达","张尧奎",80.6,"临时施工用电不符合JGJ46-2005规范,未按三级配电,二级保护要求配置电箱,缺未端电箱,电线架设不符要求,电线随意拖拉,电线破皮老化严重,脚手架搭设不符合要求,拉结点少,内档防护不到位,部份楼层临边,预留洞口等防护不到位,部份特殊工种人员操作证过期,无复审记录,现场文明施工差,材料,建筑垃圾堆放较乱,安全警示警告标志少,消防器材少,现场安全资料记录不全,"
23,"苏地2007-G-1地块地下车库",,"苏州公明监理","蔚宇兵","江阴璜塘","陈玉忠",,83.5,"临时施工用电不符合JGJ46-2005规范,未按三级配电,二级保护要求配置电箱,部份缺未端电箱,电线架设不符要求,电线随意拖拉,部份基坑边,预留洞口等防护不到位,支模排架搭设不规范,缺剪刀撑,部份特殊工种人员操作证过期,无复审记录,现场文明施工差,材料堆放较乱,安全警示警告标志少,消防器材少,"
24,"苏地2005-B-40地块","虎丘路","三联建设","缪锦贤","苏州五建","林平洋","惠忠良姜强",76,"临时施工用电不符合JGJ46-2005规范,未按三级配电,二级保护要求配置电箱,缺未端电箱,电线架设不符要求,电线随意拖拉,电线破皮老化及电箱破损严重,脚手架搭设不符合要求,拉结点少,内档防护不到位,部份楼层临边,基坑边,预留洞口等防护不到位,部份特殊工种人员操作证过期,无复审记录,现场文明施工差,材料,建筑垃圾堆放较乱,安全警示警告标志少,消防器材少,现场安全资料记录不全,生活区宿舍内较脏乱差,有烧煮现象."
25,"翻建教学综合楼","二十四中","中润监理","王健","建设集团","张振兴","王金贵",75,"少量工人在现场整理,尚未正常施工"
26,"南兵营地块项目",,"城建开发监理","钱钦宇","吴中建设","柴艳雄","王庆华陆巧平",81,"临时施工用电不符合JGJ46-2005规范,部份机具缺未端电箱,部份电箱内元器件破损未及时更换,修复,部份脚手架内档防护不到位,拉结点少,架体上建筑垃圾未及时清除,部份楼层临边,预留洞口防护不到位,现场文明施工差,材料,垃圾堆放较乱,部份特殊工种人员操作证过期,无复审记录,现场消防器材少,安全警示警告标志少,安全资料记录不全."
27,"太阳广场","石路商业广场北","晨阳监理","王光居","南通建工","邱海兵","刘 伟",,"桩基施工,未打分"
28,"苏州市大德(山塘)小学",,"苏州金泰建设咨询","樊进佳","苏州五建","陈卫","严雪峰吴永根",85.1,"临时施工用电不符合JGJ46-2005规范,部份机具缺未端电箱,部份电箱内元器件破损未及时更换,修复,部份脚手架内档防护不到位,拉结点少,架体上建筑垃圾未及时清除,部份楼层临边,预留洞口防护不到位,部份特殊工种人员操作证过期,无复审记录,现场消防器材少,安全警示警告标志少,安全资料记录不全."
29,"西中市地下停车场及恢复地面建筑工程",,"中润监理","沈士峰","苏州二建","徐峰","曹兆俊",75.4,"临时施工用电不符合JGJ46-2005规范,未按三级配电,二级保护要求配置电箱,缺未端电箱,电线架设不符要求,电线随意拖拉,电线破皮老化及电箱破损严重,脚手架搭设不符合要求,拉结点少,内档防护不到位,部份楼层临边,基坑边,预留洞口等防护不到位,部份特殊工种人员操作证过期,无复审记录,现场文明施工差,材料,建筑垃圾堆放较乱,安全警示警告标志少,消防器材少,现场安全资料记录不全,"
30,"危房翻建工程(东来仪)","清洲观前","苏州现代监理","栾长发","江苏沙家浜建筑","陈龙根","袁建忠",,"钢结构施工完毕,等验收,目前无工人作业"
31,"锦地广场",,"苏州现代监理","张洪军","吴中建设","钱晓锋","马珩 王军红",80.1,"临时施工用电不符合JGJ46-2005规范,部份电箱内元器件破损未及时更换,部份机具缺未端电箱,电线架设不符要求,部份楼层临边,预留洞口防护不到位,现场文明施工差,材料堆放较乱,部份特殊工种人员操作证过期,无复审记录,安全资料记录不全不细,"
32,"吴城分局办公楼局部修缮改造",,"苏州中润","顾志康","苏州柯利达","周卫龙","盛卫忠",80.5,"临时施工用电不符合JGJ46-2005规范,部份电箱内元器件破损未及时更换,部份机具缺未端电箱,电线架设不符要求,脚手架拉结少,内档防护不到位,部份阴角缺立杆,架体上建筑垃圾未及时清除,部份楼层临边,预留洞口防护不到位,部份特殊工种人员操作证过期,无复审记录,安全资料记录不全不细,"
33,"平江区市民活动中心室内外改造装修项目",,"苏州现代监理","张洪军","金鼎装饰","谈伟丰","潘晓瑜",,"未打分"
34,"新建平江实验学校地下停车场",,"晨阳监理","周家胜","苏州五建","梅成斌","李三男",,"未打分"
35,"美罗周边地块土建,安装工程","观前街美罗商城东","建设监理","胡春燕","苏州二建","王庆生","朱劲松朱俊荣",86.5,"个别电箱接地线不符合要求"
36,"新建箓葭巷停车场及周边配套工程",,"苏州和信","张家彬","江苏沙家浜建筑","赵敏锋","徐正良",78,"切断机用漏电保护器代替随机开关,跑到防护不到位,资料不全"
37,"三元新村中区一中分校",,"中润监理","戈华","苏州二建","张皓良","聂伟",79.9,"脚手架拉结偏少,个别消防器材过期,接地线不符合要求"
38,"苏州土地交易中心","干将西路地产大厦西侧","建筑监理","段苏华","苏州二建","吴文龙","叶红祥",90.3,"个别电线拖地,班组活动记录无"
39,"浩华置业商业用房","干将桥","天狮监理","赵喜军","苏州建鑫","王正德","徐兴涛钱志鹤",78,"基坑临边防护不到位,局部洞口无防护,坑边堆载过多"
40,"沿海国际空调通风,消防工程","干将路","上海现代监理","朱华东","中铁建工北京安装","张小兵","及翼展",,"未打分"
41,"娄门集贸市场改建",,"志成监理","祝承钦","江苏华创","吴金龙","倪建明",75.6,"外脚手拉结偏少,内脚手不规范,井架防护棚不到位,电线老化,个别机械缺开关箱"
42,"凤凰建材城","坝基桥西侧","城建开发监理","王忠荣","南京一建","宗兰君","谢建民殷振华",74,"扫地杆局部缺失,内挡防护不严密,阴角立杆缺失,局部脚手搭设滞后,临边防护不到位,塔吊基础积水"
43,"干部保健中心门诊大楼土建工程",,"苏州天狮建设监理","童红庆","苏州建设集团有限责任公司","王震","吴向东",85.6,"后浇带未封盖,用电方案未备案,扫地杆设置不符合要求"
44,"干部保健中心门诊大楼安装工程",,"苏州天狮建设监理","童红庆","江苏顺通建设公司","夏德岐","李才红",,"未打分"
45,"物理,电子实验教学楼","十梓街一号","江苏赛华建设监理有限公司","储开春","苏州二建建筑集团公司","甘宗华","戴雪东",,"未打分"
46,"物理,电子实验教学楼铝合金门窗,幕墙工程","十梓街一号","江苏赛华建设监理有限公司","莫九来","华丽美登装饰装璜有限公司","孙宏林","汝其安",,"未打分"
47,"八宝街20号1幢,3幢居民住宅用房翻建工程","八宝街","苏州天狮建设监理","童红庆","镇江建工建设集团有限公司","曹守成","王俊国",73,"配电间接地线偏小,个别电箱接线不规范,临时用电未验收,用电档案乱,食堂无卫生许可证,健康证"
48,"新建综合楼工程","苏州市沧浪区","苏州市科正工程管理咨询有限公司","卢为岭","苏州四建沧浪建筑工程公司","顾韦枫","毕利娟",73,"脚手架缺拉结,内挡缺防护,楼梯段,平台临边无防护,井架无防护棚,搅拌机使用倒顺开关,传动部位无防护罩,缺单机开关箱"
49,"综合楼","南门路48号","苏州中大监理公司","倪建青","苏州新昌建筑市政工程公司","陆凤元","王震",76,"脚手架缺拉结,内挡缺防护,井架防护棚不到位,临时用电较乱,缆风绳不规范"
50,"市场监督业务用房工程","南环路","苏州建设监理","孟祥珍","苏州一建","韩伟","侯雷 谢磊磊",86.4,"部分电箱门未接零保护,触保器试跳记录不全,施工电梯抖动,北部脚手拉结不均匀,脚手排片垃圾未清理,脚手内挡二层楼面未设置,灭火器无效,宿舍有烧煮,电梯司机证无复审记录."
51,"联青村社区服务中心工程",,"苏州相城建设监理公司","宦俊","苏州建设集团有限责任公司","张林元","钱兴生",83.3,"少数电箱门铰链坏,门未接零,试跳记录不全,圆盘锯无防护罩,木花未及时清理,模板堆放较乱,脚手密目网不全,模板与脚手连接,操作架未贯通,通道不畅,平台围护不严."
52,"苏地2005-B—1号地块综合用房项目二期","南环东路1#,3#","株洲建设监理咨询有限公司","刘文胜","苏州第一建筑有限公司","王中华","杨立军",77.2,"脚手剪刀撑不到位,内挡防护不全,排电不全,部分架子有下沉,密目网陈旧,洞口临边防护不全,模板无扫地杆,材料堆放较乱,个别砼机传动部位无防护,井架楼层平台防护门无效,钢筋机械无防护棚,部分电箱未接零,试跳记录不全."
53,"吴中大厦工程","人民南路73号","南京工大建设监理公司","蔡东星","苏州建设集团","钱伟","王仁华",83.4,"1台钢筋机械无防护棚,电箱门接零不全,试跳记录不全,多路配电无标记,塔吊指挥仅1人,脚手内挡防护上部未到位,"
54,"人民南路70号地块二期住宅","南环西路","浙江东南","吕述中","江苏兴港建设","沈玉兴","沈裕军",78.7,"现场电线架设较乱,有用塑套线,一砼机电箱破旧无门,井架围网破损,楼层安全门无效,一卷扬机前桩,脚手内挡防护不全,拉结只拉不撑,临边防护不严密,现场不整洁,复工前检查无记录."
55,"公共交通信息中心大楼的土建水电工程",,"中咨工程建设监理公司","李鸿","苏州二建建筑集团公司","李文涵","宋峻",84.7,"钢筋绞丝机设备位置妥,无防护棚,砼机传动部位防护罩不全,钢丝绳缺油,电箱门部分未接零,试跳记录不全,安全网围护不严密,脚手立杆接头部分在一个水平上."
56,"改建友联经贸大厦","解放东路555","中润监理","张浩","南通光华","储开俊","朱兵",80.7,"钢筋切断机电箱无隔离开关,接零保护未贯通,钢筋机械,木工机械无防护棚,塔吊基础有积水,东施工电梯处一灭火器失效,楼层有积水,试跳记录不全,临边防护一处未到位,管道井防护较差,脚手密目网破损,宿舍烧煮严重,电梯司机上岗证不足."
57,"苏州运政指挥中心(内外装饰)工程",,"苏州三联建设顾问有限公司","王少君","苏州市华丽美登装饰装潢有限公司","侯俊","黄建国",85.5,"脚手拉结应加强,排片上建筑垃圾应清理,个别灭火器已失效,楼层平台上垃圾多,排片铺设不全,试跳记录不全."
58,"苏州运政指挥中心工程","桐径南路和南环西路交叉处","苏州三联建设顾问有限公司","姚元录","苏州第五建筑公司","朱林福","戴秋冬","已基本结束","宿舍卫生差,有烧煮现象,塔吊基础有积水,砼机传动部位无防护罩,地下室顶板上积水."
59,"新郭创业中心大厦工程","友新路西","苏州中润建设监理","于寒","苏州五建","胡寄平","马剑鸣",79.6,"塔吊基础积水,井架卷扬机绳筒钢丝绳短,个别设备接零未贯通,电箱无试跳记录,露台上外脚手立杆有吊脚,扫地杆不全,局部电梯井口安全门被拆."
60,"电信模块局(含移动基地)及公厕","沧浪新城","苏州中大监理公司","潘立念","苏州市顺发建设有限公司","王金明","徐良良",73.2,"卷扬机电箱门已坏,井架卷扬机钢丝绳铁锈,井架楼层无安全门,试跳记录未见,场地不整洁,脚手架内倾,西面无拉结,扫地杆不全."
61,"四季晶华社区服务中心工程","沧浪新城","苏州中大监理公司","唐建国","苏州第一建筑有限公司","刘震","卫建强",90.4,"脚手架内挡防护不当,露台脚手架扫地杆被拆除,电箱试跳记录未见."
62,"消防站建设工程","沧浪新城","苏州现代建设监理有限公司","刘臻","苏州第五建筑公司","徐建军","顾建良",84.8,"北井架少一道揽风,北井架电箱保护接零未与重复接地贯通,钢筋棚灭火器已失效,南工程通道口未设置,临边防护不严密,南楼北脚手二,三步处内挡亦应设防护栏杆."
63,"垃圾中转站工程","沧浪新城","江苏众信工程投资项目管理咨询公司","胡洪兴","苏州凤凰建筑安装工程有限公司","李志超","丁建平",70.8,"井架楼层无安全门,重复接地不到位,电箱未按规定设置,碘钨灯无接零保护,脚手拉结少,扫地杆设置不符,通道未硬化,材料堆放乱."
64,"市中医院工程","沧浪新城","苏州中润监理","汪若峰","苏州一建","何新伟","冯德",76.9,"井架安全门无效,塔吊基础积水,木工间木花未及时清理,部分电箱门未接零,电箱试跳记录不到位,八楼局部临边无围护,楼层洞口无围护,电梯井立面平台围护不符合,模板纵横杆不全,脚手内挡防护不全,排片不贯通,宿舍烧煮严重,复工前检查教育记录无."
65,"苏州世茂运河城一期工程","宝带西路与新郭路立交路口","上海三维工程建设咨询公司","金建刚","中建三局第三建设工程公司","顾小强","黄火青",72.7,"现场积水,泥泞,塔吊,电梯积水严重,分电箱未重复接地,电箱门未接零,试跳记录不全,保护接零有不到位,材料堆放较乱,设备防护棚不全,洞口无防护,电梯井防护不全,悬挑梁钢丝绳设置不严,宿舍烧煮现象严重."
66,"苏州世茂沧浪新城一期工程",,"上海三维工程建设咨询公司","金建刚","中国建筑第八工程局","柴于飞","王云",73.6,"开关箱动力,照明混用,触保器2只失灵,试跳无记录,一分电箱无门,5号房三层阳台无围护,脚手架内挡无防护,排片不全,局部洞口无围护,塔吊基础有积水现象,施工电梯检测报告未提供."
67,"苏州世茂运河城16#17#地块",,"上海三维工程建设咨询公司","金建刚","上海宝冶","丁海涛","夏树军","挖土阶段","触保器试跳失灵."
68,"苏地2005-B-3号地块住宅及商业用房工程","宝带西路北侧","苏州联信工程管理咨询公司","徐进波","上海汇成建设发展公司","孙斌","唐云康",73.2,"脚手架拉结点偏少,安全网封闭不严,悬挑梁缺固定螺帽,楼层预留洞未防护,塔吊基础积水."
69,"山水映象二期A标","学府路,科技路","上海新光","朱伟","浙江展诚建设集团有限公司","周洪钊","沈国鹏",81.3,"临时用电电箱损坏严重,电线路直接绕在脚手架上,切割机无末端开关箱,井架通道口防护不严,出料口大部分无安全门,施工地段积水严重."
70,"新校区工科组团A区(物理生物化学实验楼)","国际教育园北区","苏州天狮建设监理","赵喜军","苏州二建建筑集团公司","谭金锁","叶建付",85.8,"塔吊回转半径内井架揽风绳影响塔吊作业,施工照明未接PE线,缺灭火机(脚手架)."
71,"新校区一期4#,5#学生宿舍组团","国际教育园北区","苏州天狮建设监理","朱孟鸿","苏州建设集团有限责任公司","吴向东","康红兵",80,"施工现场材料堆放不整齐规范,临时用电线路架设不规范,有拖地现象,专用保护零线有漏接现象,宿舍区生活垃圾未及时清理."
72,"苏州经贸职业技术学校新校区二期食堂,活动中心和学生宿舍工程","国际教育园北区","苏州中润建设管理咨询公司","沈士峰","苏州二建","陈晓锋","程兵",86.8,"井架揽风绳设置不合理,用电线路未架设,通道口防护棚太小."
73,"新校区教学用房工程一标段","国际教育园北区","苏州现代建设监理公司","范维严","苏州嘉盛建设工程有限公司","石忠华","宋金林",81.6,"塔吊作业无指挥人员,塔吊无吊钩保险,大量电线存在拖地现象,末端开关和二级箱内的PE线未连接,搅拌机无防雨棚及操作规程."
74,"汽车实训中心建设工程","国际教育园北区","苏州现代建设监理有限公司","赵幌宏","苏州二建","李小峰","郑文军",83.5,"脚手架防护有漏缺现象,临时用电线路存在拖地现象,井架出料口防护不严."
75,"新建学员活动用房","劳动路599号","苏州中大监理公司","尤永斗","苏州第一建筑有限公司","赵有军","李尔辉",92.25,"塔吊基坑积水,塔吊司机上下班通道堆放材料,钢筋,木工未搭设防护棚,临时用电线路架设不规范."
76,"中海胥江府","胥江路","天狮建设监理","郑传明","长业建设集团","刘华平","刘佰林",77.3,"施工升降机门电联装置失效,减速机漏油,脚手架安全网防护不到位,架上垃圾较多,部分缺扶手,电梯井口防护门未定型化,工具化."
77,"中海胥江项目5#—13#半地库一(二)期,半地库,幼儿园","胥江路","苏州天狮建设监理","郑传明","苏州第五建筑公司","钱爱民","张菊新",84,"临时用电配电系统中PE有漏接现象,电焊机未使用末端开关箱,楼层烟道口未进行防护,木工间圆盘锯末端箱不符."
78,"苏州供电公司生产营业调度综合用房(总承包)工程","劳动路69号","苏州建设监理有限公司","郁文捷","苏州二建","陈国良","吕纯",,"基础施工未打分"
79,"金色家园二期","劳动路冶金厂","上海天佑监理","杨玉军","上海住总集团","沈三新","张瑜",80,"脚手架内挡防护不严及建筑垃圾较多,施工现象排水不畅有积水."
80,"金螳螂设计研究中心幕墙工程",,"苏州天狮建设监理","吴宪章","苏州金螳螂建筑装饰股份有限公司","吴基刚","王群峰",75.3,"临时用电配电线路架设不规范,电线未架设,切割机,套丝机无末端开关箱,消防器材不足,无复工报告,楼层临边无防护措施,架子拉结点偏少,无防护杆."
81,"苏州市残疾康复楼装修工程","索山大桥东堍北侧","苏州天狮建设监理","王虹","苏州国贸嘉和建筑工程有限公司","王蕾","王秀中",87,"配电线路出线未标识,采用材料线,"
82,"双桥村村委会及社区办公服务综合用房工程","西环路","中润建设管理咨询公司","陈网晓","苏州五建","张家怡","周火根",,"基础施工,未打分,"
83,"苏州分公司城西通信指挥中心副楼工程","三香路1036号","时代工程咨询设计管理","胡忠良","苏州二建","周文","蔡汉中",86.4,"井架第一道附墙装置拆除,井架出料口防护不严,防护门未关闭,施工现场材料堆放不整齐,脚手架上堆放石材超过规定."
84,"2005-B—41地块商业办公用房工程","阊胥路烟草公司对面","苏州建设监理有限公司","马树奇","南通英雄建筑安装工程有限公司","张华","沈建华",75.6,"模板支撑系统不符合要求,高支模无方案及专家论证,脚手架拉结点偏少,不符合规范要求,塔吊基坑积水."
85,"苏州市纪检监察固定办案场所","盘门路344号","中润建设管理咨询公司","金桂林","江苏金土木华亭","周利中","任雪明",82.1,"井架附墙装置连接不符要求,其中西侧井架的导向滑轮磨损不正常,宿舍区不整洁,卫生状况差,临时用电线路过路保护不符合要求."
"市政"
"市区市政工程安全生产与文明施工(一季度)项目检查汇总表"
"序号","项 目 名 称","项目地点","监理单位","总监","施工单位","项目 经理","安全员","检查 得分","备注(存在主要问题)"
1,"江宙路道路工程","苏站路北侧","建设监理","董根法","市政设施管理处","徐原根","谢 晓",81.5,"氧气瓶与乙炔瓶不满足安全距离,每周自查应由项目经理带队进行"
2,"江乾路二期道路工程",,"南京旭光","江永军","苏州二建","吴诗怡","张炎",85.8,"桥梁作业区上下人员通道强度差,电线架设不符合要求"
3,"金三路,金五路,金民东路,苏四路",,"晨阳监理","郁离炎","南京嘉盛","陈维圣","朱承海","整改 合格","资料混乱,项目经理不到位,用电无交接手续"
4,"江月路道路工程",,"天狮监理","陆军","水城市政","朱哲理","戈学明",86.7,"个别电箱接地不符合要求,承台周边防护不到位"
5,"火车站站前高架匝道及清新路工程",,"江苏华宁交通","杨爱宝","青岛第一市政","吕方平","朱吉禄",72.2,"高支模方案专家论证滞后,路面泥泞"
6,"平泉路(清新路)道路,桥梁,排水工程",,"江西中昌监理","杨明","水城市政","张敏","徐卫",87.7,"窨井盖防护不严密"
7,"平江新城斜河浜(北段)河道整治",,"水利监理","杨胜勇","水城市政","郑 栋","王进","未打分","停工阶段"
8,"苏州平川路道路工程",,"江西中昌监理","晏农芳","苏州市政工程集团","陈优","裘凤岐",85.6,"电线老化,基坑通道,桥台作业平台防护不到位"
9,"新莲路金阊段一标","新莲路","建设监理","葛奇","苏州市政集团","钱建平","韩明春",86.2,"桥台临边防护不到位"
10,"新莲路金阊段排水,桥梁(三标)工程",,"南京旭光","朱柏元","杭州萧红建设","童晓东","陈君军",77,"搅拌机防护罩缺失,PE线未贯通,开关箱中缺隔离开关"
11,"金阊新城白洋湾公园",,"上海斯美科汇","姚荣明","苏州建设集团","邢志勇","秦通祥",85.3,"基坑支护方案专家论证滞后,挖掘机司机操作证不全"
12,"阳山东路跨线桥一标",,"华铁监理","宗玉昌","中铁二十四局","阙黎明","程新民",78.3,"项目经理不到位,上下高架斜道刚度不足"
- 建筑装饰施工试卷 > "2009年市区建筑工程安全生产与文明施工(一季度)项目检...
-
"2009年市区建筑工程安全生产与文明施工(一季度)项目检...
下载该文档 文档格式:XLS 更新时间:2010-10-07 下载次数:0 点击次数:30文档基本属性 文档语言: Simplified Chinese 文档格式: xls 文档作者: g 关键词: 主题: 备注: 点击这里显示更多文档属性 经理: 单位: 分类: 创建时间: 2003-06-03 02:38:27 上次保存者: 修订次数: 编辑时间: 文档创建者: 修订: 加密标识: 幻灯片: 段落数: 字节数: 备注: 演示格式: 上次保存时间:
- 下载地址 (推荐使用迅雷下载地址,速度快,支持断点续传)
- XLS格式下载
- 更多文档...
-
上一篇:南宁市第一职业技术学校装饰基础试卷
下一篇:深圳市建筑装饰工程施工合同
点击查看更多关于建筑装饰施工试卷的相关文档
- 您可能感兴趣的
- 建筑装饰材料试卷 建筑装饰构造试卷 建筑装饰施工合同范本 建筑装饰装修施工规范 建筑装饰装修施工合同 建筑装饰装修施工方案 建筑装饰装修工程施工 建筑装饰工程施工合同 建筑装饰施工技术
- 大家在找
-
- · 新概念英语第一册听力
- · 可牛下载2011
- · 电涡流式传感器的静态标定
- · asp网页制作教程
- · 江西农业大学教务网
- · 通信与用电技术分公司
- · 右侧超车发生刮蹭责任
- · 二保焊焊接视频
- · 英语四级词汇视频教程
- · autocad2005电气
- · 化工原料批发
- · 2010常州化学中考
- · 新港海关缉私分局
- · 电影天堂迅雷下载mp3
- · 沈阳到本溪一日游价钱
- · 服务器设置
- · 东莞新德镀膜科技有限公司
- · 2kill4掐毙
- · 北京天通苑社区网
- · 电力电子自动控制系统
- · 道德修养与个人发展
- · 高低压电器元件
- · cyclo
- · 基于plc抢答器的设计
- · c++语言程序设计
- · 317,,30,"固体化学","限选",36,"焦秀玲",,"√"管理学原理课件
- · 四川省南部县邮编
- · 青少年上网成瘾危害
- · 百里挑一谢梦牵手
- · excel表格按姓氏排序
- · 四大职教模式doc
- · 日本取精图片
- · 深圳经济特区第四轮市区政府投资事权划分实施方案
- · 肿瘤的早期症状
- · 步步高学习机h3
- · 去年初一月考试卷
- · accp6.0课件下载
- · 人际沟通技巧ppt
- · 高二期末试题
- · 环境管理体系内审员
- 赞助商链接